Page 22 / 23
4
FUNCTIONS
4.1.
Application
Control
The controller is designed for multi-application cabinets. For instance, universal cabinets where the
user can change the unit from freezer to cooler mode just by pressing a button or by changing a single
parameter.
Up to 5 applications can be defined. Each application contains basically any setting for a specific
application, such as freezer, cooler, dairy products, meat, or night operation. Applications can be changed
via the local display, Modbus, external switch, or internal timer.
The following parameters can be set:
>
Temperature settings: set points, offsets, time constants, sensor weighting
>
Alarms: Which alarms should be reported and were, limits, delay of alarms
>
Defrost control, defrost scheduling
>
Relay usage
>
Sensors, time constants, offsets
>
User interface: resolution of temperature, temperature unit, definition of buttons
>
Peripherals, fans, light, heaters
How to manage applications:
1. Enable the number of applications you need. If only 2 are needed, then enable 2 and disable the
remaining
2. Name the applications to get a better overview in Tool4Cool
®
3. Select the application to edit the parameters
4. Go through the settings one by one
5. When finished, switch to the next application and repeat (4) until all (enabled) applications have been set
Parameter Function Code Min. Max.
Default
Setting
Application selection via MMI and remote
0: Application 1
1: Application 2
2: Application 3
3: Application 4
4: Application 5
P10 0 4 0
Application 1 selectable P01 0 1 1
Application 2 selectable P02 0 1 0
Application 3 selectable P03 0 1 0
Application 4 selectable P04 0 1 0
Application 5 selectable P05 0 1 0
Selected application (Read only)
0: Application 1
1: Application 2
2: Application 3
P20 0 4 RO
Application selection via DIO P27 0 5 0
Application 1 nighttime P21 0 (none) 5 0
Application 2 nighttime P22 0 (none) 5 0
Application 3 nighttime P23 0 (none) 5 0
Application 4 nighttime P24 0 (none) 5 0
Application 5 nighttime P25 0 (none) 5 0
Application active timer P28 0 5 0