UL 864 Permitted Configurations F
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
116 of 127
Notice To Users, Installers, Authorities Having Jurisdiction, and other involved parties.
This product incorporates field-programmable software. In order for the product To comply with the requirements in
the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 10th Edition, certain programming
features or options must be limited To specific values or not used at all as indicated below.
Program Feature or Option Permitted in UL 864 ? (Y/N) Possible Settings Settings Permitted
In UL 864
NAC Output Delay
Code: C00 To C09
N 30 seconds - 9 minutes 0 minutes
Zone 1 and Zone 2 Detectors
Trigger Automatic Release
Code: C11
Y Enable / Disable Enable / Disable
Zone 2 and Zone 3 Detectors
Trigger Automatic Release
Code: C12
Y Enable / Disable Enable / Disable
Zone 1 and Zone 3 Detectors
Trigger Automatic Release
Code: C13
Y Enable / Disable Enable / Disable
Zone 1 and Zone 2 or
Zone 2 and Zone 3 or
Zone 1 and Zone 3 Detectors
Trigger Automatic Release
Code: C14
Y Enable / Disable Enable / Disable
Zone 1 and Zone 2 and
Zone 3 Detectors Trigger
Automatic Release
Code: C15
Y Enable / Disable Enable / Disable
Zone 1 or Zone 2 or Zone 3
Detectors Trigger Automatic
Release
Code: C16
Y Enable / Disable Enable / Disable
Appendix F
UL 864 Permitted Configurations