UL 864 Permitted Configurations F
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
117 of 127
Program Feature or Option Permitted in UL 864 ? (Y / N) Possible Settings Settings Permitted
In UL 864
Zone 1 Triggers
Automatic Release
Code: C17
Y Enable / Disable Enable / Disable
Zone 2 Triggers
Automatic Release
Code: C18
Y Enable / Disable Enable / Disable
Zone 3 Triggers
Automatic Release
Code: C19
Y Enable / Disable Enable / Disable
Fire Buzzer
Code: C21
N Enable / Disable Enable
Fire Output
Code: C22
N Enable / Disable Enable
Trouble Output
Code: C23
Y Enable / Disable Enable
Ground Trouble
Code: C24
N Enable / Disable Enable
Pulse R0V Output
Code: C25
Y Enable / Disable Enable / Disable
Remove AUX 24V On
System Reset
Code: C26
Y Enable / Disable Enable / Disable
Indicating Exting Released
When Exting Output Is
Active
Code: C27
Y Enable / Disable Enable / Disable
No Activation Delay Upon
Manual Release
Code: C28
Y Enable / Disable Enable / Disable