UL 864 Permitted Configurations F
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
118 of 127
Program Feature or Option Permitted in UL 864 ? (Y / N) Possible Settings Settings Permitted
In UL 864
Extinguishant Output Can
Be Reset During Imminent
Phase
Code: C29
Y Enable / Disable Enable / Disable
Local Fire Relay Operates
Upon Released Signal
Code: C2A
Y Enable / Disable Enable / Disable
Extinguishing Output On
Until Reset
Code: C2b
Y Enable / Disable Enable / Disable
Low Pressure Switch
Normally Closed
Code: C2C
Y Enable / Disable Enable / Disable
Zone 1 Alarm From Detector
Delayed
Code: C31
N Delay Options 0 To 9 Option 0 to disable
Zone 2 Alarm From Detector
Delayed
Code: C32
N Delay Options 0 To 9 Option 0 to disable
Zone 3 Alarm From Detector
Delayed
Code: C33
N Delay Options 0 To 9 Option 0 to disable
Zone 1 Alarm From
Pull Station Delayed
Code: C41
N Delay Options 0 To 9 Option 0 to disable
Zone 2 Alarm From
Pull Station Delayed
Code: C42
N Delay Options 0 To 9 Option 0 to disable
Zone 3 Alarm From
Pull Station Delayed
Code: C43
N Delay Options 0 To 9 Option 0 to disable