UL 864 Permitted Configurations F
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
119 of 127
Program Feature or Option Permitted in UL 864 ? (Y / N) Possible Settings Settings Permitted
In UL 864
Zone 1 Operates Through
I.S. Barrier
Code: C61
N Enable / Disable Disable
Zone 2 Operates Through
I.S. Barrier
Code: C62
N Enable / Disable Disable
Zone 3 Operates Through
I.S. Barrier
Code: C63
N Enable / Disable Disable
Zone 1 Short Circuit
Indicates Alarm
Code: C71
Y Enable / Disable Enable / Disable
Zone 2 Short Circuit
Indicates Alarm
Code: C72
Y Enable / Disable Enable / Disable
Zone 3 Short Circuit
Indicates Alarm
Code: C73
Y Enable / Disable Enable / Disable
Zone 1 Non-Latching
Code: C81
N Enable / Disable Disable
Zone 2 Non-Latching
Code: C82
N Enable / Disable Disable
Zone 3 Non-Latching
Code: C83
N Enable / Disable Disable