UL 864 Permitted Configurations F
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
120 of 127
Program Feature or Option Permitted in UL 864 ? (Y / N) Possible Settings Settings Permitted
In UL 864
Zone 1 Device Alarm Must
Be Present For 30 Seconds
Code: CA1
N 0 To 30 Seconds Option 0 to disable
Zone 2 Device Alarm Must
Be Present For 30 Seconds
Code: CA2
N 0 To 30 Seconds Option 0 to disable
Zone 3 Device Alarm Must
Be Present For 30 Seconds
Code: CA3
N 0 To 30 Seconds Option 0 to disable
Panel Can Be Reset
Immediately After Discharge
Output Has Operated
Code: E00
Y Enable / Disable
Enable / Disable
Panel Can Be Reset 1
Minute To 29 Minutes After
Discharge Output Has
Operated
Code: E01 To E29
Y 1 To 29 Minutes 1 To 29 Minutes
Panel Can Be Reset
30 Minutes After Discharge
Output Has Operated
Code: E30
Y Enable / Disable Enable / Disable