UL 864 Permitted Configurations F
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
121 of 127
Program Feature or Option Permitted in UL 864 ? (Y / N) Possible Settings Settings Permitted
In UL 864
No Extinguishant Delay
Code -00
Y Enable / Disable Enable / Disable
5 Second Extinguishant
Delay
Code: -05
Y Enable / Disable Enable / Disable
Increment Extinguishant
Delay In Five Second Steps
Code: -10 to -55
Y 10 To 55 Seconds 10 To 55 Seconds
60 Second Extinguishant
Delay
Code: -60
Y Enable / Disable Enable / Disable
Extinguishant Delay
In 5 Second Steps
Code: 60
Y 0 To 60 Seconds 0 To 60 Seconds
Increment Extinguishant
Duration In Five Second
Steps
Code: 60 to 295
Y 60 To 295 Seconds 60 To 295 Seconds
Extinguishant Duration
In 5 Second Steps
Code: 300
Y 60 To 300 Seconds 60 To 300 Seconds

Table of Contents