- 21 -
5-26 Event 3 (EV3) hysteresis setting screen
 To 5-0 screen
  Initial value: 5
 Setting range: 1 ~ 999 digits
The explanation on 5-20 screen applies to this screen except EV1
changed to EV3.
5-27 Event 3 (EV3) standby action code setting screen
 To 5-0 screen
  Initial value: 1
 Setting range: 1 ~ 4
The same as the 5-21 screen EV1 changed to EV3.
(15) Setting Status Output (DO)
5-28 Status output 1 (DO1) action code setting screen
To 5-0 screen
  Initial value: NON
Setting range: ~  
A code to be set as DO1 is selected from the following table:
Table of Status Output Action Type Codes
Code Description
 None
 Scaleover, Hold
 Hold
| Guarantee soak
i Time si
g
nal 1
j Time si
g
nal 2
 RUN status
 Ste
p
si
g
nal
~ End signal
 FIX
5-29 Status output 2 (DO2) action code setting screen
To 5-0 screen
  Initial value: NON
 Setting range: 
The same as the 5-28 screen except DO1 changed to DO2.
5-30 Status output 3 (DO3) action code setting screen
To 5-0 screen
  Initial value: NON
 Setting range: 
The same as the 5-28 screen except DO1 changed to DO3.
5-31 Status output 4 (DO3) action code setting screen
To 5-0 screen
  Initial value: NON
 Setting range: 
The same as the 5-28 screen except DO1 changed to DO3.
5-32 Status output type setting screen
To 5-0 screen
  Iitial value: 
 Setting range: , , 
The same as the 5-28 screen except DO1 changed to DO3.
5-33 Analog output scaling lower limit setting screen
To 5-0 screen
  Initial value: The lower limit value of setting range for
 PV and SV, and 0.0 for OUT
 Setting range: Within measuring range when PV or SV
 is selected and 0.0 ~ 100.0% when OUT
 is selected.
A minimum value (0mV, 4mA or 0V) of analog output signal is set
at a value intended to be output as the lower limit value of scaling.
To 5-34 screen
5-34 Analog output scaling higher limit setting screen
To 5-0 screen
  Initial value: The higher limit value of setting range for
 PV and SV, and 100.0 for OUT
 Setting range: Within measuring range when PV or SV
 is selected and 0.0 ~ 100.0% when
 OUT is selected.
A minimum value (10mV, 20mA or 10V) of analog output
signal is set at a value intended to be output as the higher limit
value of scaling.
Inversed scaling of Ao_LAo_H is also possible.
In the case of Ao_L Ao_H In the case of Ao_L Ao_H

(17) Setting Communication
Note: For communication, refer to the Communication Interface
 Instruction Manual provided separately.
5-35 Communication mode setting screen
To 5-0 screen
 Initial value:
Setting range : (LOC), }(COM)
The following selections can be made for communications.
In COM 1 mode, change from LOC to COM by key operation is
possible.
When COM 2 mode is selected, change from LOC to COM by
key operation is impossible
5-36 Communication protocol Setting
To 5-0 screen
 Initial value:
Setting range : (Shim), |(Asc),
(RTU)
Shim: Shimaden standard mode
asc: MODBUS ASCII mode
rtu: MODBUS RTU mode
Select either one of the communication protocols.
5-37 Communication address setting screen
 To 5-0 screen
 Initial value:1
 Setting range: 1 ~ 255
A machine number is set in case two or more controllers are
connected through communication.
5-38 Communication speed setting screen
 To 5-0 screen
 Initial value: 1200
 Setting range: 1200, 2400, 4800, 9600, 19200 bps
The speed of communication is set.
Note 1: Because of a limited number of digits, 19200 bps is
displayed as i{j.
Note 2: Special keys on the communication speed screen:
When the key and the key are pressed
simultaneously for 3 seconds on this screen, the present
speed is forcibly changed. This interrupts communication
and the mode is changed from communication to local.
To restart communication, the same speed as that of the
host has to be set.
To 5-39 screen

~k¦

~k¦

i
i

j

k

|¦
phrh
100
Analog out put
0
0 Ao_L Ao_H 100 0 Ao_ H Ao_ L 100
Scaling range
Scaling range




|

i
l

|¦


|¦

rh

ijhh