10 TROUBLESHOOTING
10.1 Checking Errors with LEDs
117
10
*1 The ERROR LED flashes rapidly and repeatedly at regular intervals.
LEDs on an FX5-SF-8DI4
Q2/Q3 LED Green Indicates the output statuses of Q2 and Q3.
ON: Output ON
Flashing: In lapse of off delay time
OFF: Output OFF
X0 LED Green Indicates the input status of X0.
ON: Input ON
Flashing: Input OFF (by restart interlock or EDM)
OFF: Input OFF
X1 LED Green Indicates the input status of X1.
ON: Input ON
Flashing: Input OFF (by restart interlock or EDM)
OFF: Input OFF
X2 LED Green Indicates the input status of X2.
ON: Output ON
Flashing: Input OFF (by restart interlock or EDM)
OFF: Input OFF
XS0 LED Green Indicates the input status of XS0.
ON: Input ON
OFF: Input OFF
LED name LED color Description
POWER LED Green Indicates the power supply status.
ON: Normal operation
Flashing: The rotary switch setting was changed during operation.
OFF: Powered OFF
ERROR LED
*1
Red Indicates an error status.
ON: An error occurred in any one of the safety extension modules.
Flashing (two times): Failed to apply the settings to the safety extension module.
Flashing (three times): The rotary switch setting was changed during operation.
Flashing (four times): Any of the following errors occurred.
The module was powered ON after the rotary switch setting has been changed in the power OFF state.
The ENTER button is pressed for three seconds or more.
A setting was not applied after changing the position of a module.
Flashing (five times): A power supply error occurred.
Flashing (six times): A self-monitoring error or an internal error occurred.
OFF: No error
I0 LED Green Indicates the input status of I0.
ON: Input ON
Flashing: A process error occurred or synchronous time (1500ms) was exceeded.
Flashing (I0 and I1 flash in phase): A cross-circuit occurred between I0 and I1.
OFF: Input OFF
I1 LED Green Indicates the input status of I1.
ON: Input ON
Flashing: A process error occurred or synchronous time (1500ms) was exceeded.
Flashing (I0 and I1 flash in phase): A cross-circuit occurred between I0 and I1.
OFF: Input OFF
I2 LED Green Indicates the input status of I2.
ON: Input ON
Flashing: A process error occurred or synchronous time (1500ms) was exceeded.
Flashing (I2 and I3 flash in phase): A cross-circuit occurred between I2 and I3.
OFF: Input OFF
I3 LED Green Indicates the input status of I3.
ON: Input ON
Flashing: A process error occurred or synchronous time (1500ms) was exceeded.
Flashing (I2 and I3 flash in phase): A cross-circuit occurred between I2 and I3.
OFF: Input OFF
I4 LED Green Indicates the input status of I4.
ON: Input ON
Flashing: A process error occurred or synchronous time (1500ms) was exceeded.
Flashing (I4 and I5 flash in phase): A cross-circuit occurred between I4 and I5.
OFF: Input OFF
LED name LED color Description