4 FUNCTIONS
4.14 Safety Information Monitoring Function
85
4
4.14 Safety Information Monitoring Function
To store information including the I/Os, settings, and error codes of a safety extension module to the buffer memory.
The safety information can be referenced by user programs and built-in functions (such as Web server) of a CPU module or
the monitoring screen of GX Works3.
Operation
This function stores information including the I/Os, settings, and error codes of a safety extension module to a buffer memory
of a safety main module.
Not only the information of a safety main module, but also the information of a safety extension module are stored in the buffer
memory.
Buffer memory to be used
The buffer memory used for this function are as shown below.
For details on the buffer memory, refer to the following:
Page 136 Buffer Memory
Address
(decimal)
Address
(hexadecimal)
Buffer memory name Data type Auto-refresh
71 47H Number of units connected Monitor
100 64H 1st Module Input signal Monitor
101 65H 1st Module Output signal and Module state Monitor
102 66H 1st Module Output signal and Internal error Monitor
103 67H 1st Module System CRC Monitor
104 68H 1st Module Input terminal error Monitor
105 69H 1st Module Error code 1 Monitor
106 6AH 1st Module Error code 2 Monitor
108 6CH 1st Module Lower Rotary Switch state Monitor
109 6DH 1st Module Upper Rotary Switch state Monitor
110 6EH 1st Module X0 terminal state Monitor
111 6FH 1st Module X1 terminal state Monitor
112 70H 1st Module X2 terminal state Monitor
113 71H 1st Module Module name identifier Monitor
115 73H 1st Module Lower Rotary Switch startup state Monitor
116 74H 1st Module Upper Rotary Switch startup state Monitor
117 75H 1st Module X0 terminal startup state Monitor
118 76H 1st Module X1 terminal startup state Monitor
119 77H 1st Module X2 terminal startup state Monitor
120 78H 1st Module Off delay time Monitor
140 8CH 2nd Module Input signal Monitor
141 8DH 2nd Module Output signal Monitor
144 90H 2nd Module Input terminal error Monitor
145 91H 2nd Module Error code 1 Monitor
146 92H 2nd Module Error code 2 Monitor
148 94H 2nd Module Lower Rotary Switch state Monitor
149 95H 2nd Module Upper Rotary Switch state Monitor
150 96H 2nd Module X0 terminal state Monitor
151 97H 2nd Module X1 terminal state Monitor
152 98H 2nd Module X2 terminal state Monitor
153 99H 2nd Module Module name identifier Monitor
155 9BH 2nd Module Lower Rotary Switch startup state Monitor
156 9CH 2nd Module Upper Rotary Switch startup state Monitor
157 9DH 2nd Module X0 terminal startup state Monitor

Table of Contents