72
4 FUNCTIONS
4.5 AND link
4.5 AND link
This function connects each input of an FX5-SF-MU4T5 and FX5-SF-8DI4 using AND logic.
Setting method
■For FX5-SF-MU4T5
Set the FUNCTION rotary switch to '5', '6', '7', or '9'.
Sensors that can be connected to an FX5-SF-MU4T5 are as follows.
: Connectable, : Not connectable
FX5-SF-MU4T5
(Program)
Inputs and sensors Description Input of logic
path A (I0, I1)
Input of logic
path B (I2, I3)
5 : Potential free contact Dual-channel equivalent N/C contact (with
cross-circuit detection)
• : Emergency stop button
• : Safety door switch
Dual-channel equivalent N/C contact (with
cross-circuit detection)
: Two-hand control switches Two-hand operation (A) without jog mode
: Two-hand control switches Two-hand operation (A) with jog mode (time
limit 5 seconds)
: Non-contact safety switch Dual-channel equivalent N/C contact
: Single-beam photoelectric safety
sensor
Dual-channel equivalent N/C contact (with
cross-circuit detection)
6 : Potential free contact Dual-channel equivalent N/C contact (with
cross-circuit detection)
• : Emergency stop button
• : Safety door switch
Dual-channel equivalent N/C contact (with
cross-circuit detection)
: Non-contact safety switch Dual-channel equivalent N/C contact
: Single-beam photoelectric safety
sensor
Dual-channel equivalent N/C contact (with
cross-circuit detection)
7 • : Potential free contact
• : Emergency stop button
• : Safety door switch
Single-channel N/C contact
• : Potential free contact
• : Emergency stop button
• : Safety door switch
Dual-channel equivalent N/C contact
: Electro-sensitive protective
equipment (ESPE)
Electro-sensitive protective equipment
(ESPE) with semiconductor output
: Inductive switch Sensor with semiconductor output (OSSD
output)
: Single-beam photoelectric safety
sensor
Dual-channel equivalent N/C contact
9 • : Potential free contact
• : Emergency stop button
• : Safety door switch
Single-channel N/C contact
• : Potential free contact
• : Emergency stop button
• : Safety door switch
Dual-channel equivalent N/C contact
: Potential free contact Dual-channel equivalent N/C contact (with
cross-circuit detection)
• : Emergency stop button
• : Safety door switch
Dual-channel equivalent N/C contact (with
cross-circuit detection)
: Electro-sensitive protective
equipment (ESPE)
Electro-sensitive protective equipment
(ESPE) with semiconductor output
: Non-contact safety switch Dual-channel equivalent N/C contact
: Inductive switch Sensor with semiconductor output (OSSD
output)
: Single-beam photoelectric safety
sensor
Dual-channel equivalent N/C contact
: Single-beam photoelectric safety
sensor
Dual-channel equivalent N/C contact (with
cross-circuit detection)