EasyManua.ls Logo

SICK MITSUBISHI ELECTRIC MELSEC iQ-F Series - Page 75

SICK MITSUBISHI ELECTRIC MELSEC iQ-F Series
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 FUNCTIONS
4.5 AND link
73
4
Page 57 Details of the program 5 for FX5-SF-MU4T5s
Page 59 Details of the program 6 for FX5-SF-MU4T5s
Page 61 Details of the program 7 for FX5-SF-MU4T5s
Page 65 Details of the program 9 for FX5-SF-MU4T5s
For FX5-SF-MU4T5 and FX5-SF-8DI4
Set the FUNCTION rotary switch of an FX5-SF-MU4T5 as necessary.
Set a rotary switch to any one of 1 to 6 depending on the sensor connected to the FX5-SF-8DI4.
Sensors that can be connected to an FX5-SF-8DI4 are as follows.
: Connectable, : Not connectable
Operation
For FX5-SF-MU4T5
Connect I0/I1 and I2/I3 of an FX5-SF-MU4T5 using AND logic.
For FX5-SF-MU4T5 and FX5-SF-8DI4
Connect a logic path of an FX5-SF-MU4T5 to an input of the FX5-SF-8DI4 using AND logic.
Precautions
To prevent the AND logic to always be '0', connect unused input terminal to a plus terminal.
FX5-SF-8DI4
(Program)
Inputs and sensors Description Input (I0 to
I3)
Input (I4 to
I7)
1 : Potential free contact
: Emergency stop button
: Safety door switch
Single-channel N/C contact 
: Single-beam photoelectric safety
sensor
Single-channel N/C contact 
2 : Potential free contact Dual-channel equivalent N/C contact (with
cross-circuit detection)

: Emergency stop button
: Safety door switch
Dual-channel equivalent N/C contact (with
cross-circuit detection)

Safety mat Pressure sensitive mat (four-wire system) 
: Non-contact safety switch Dual-channel equivalent N/C contact 
: Single-beam photoelectric safety
sensor
Dual-channel equivalent N/C contact (with
cross-circuit detection)

3 : Potential free contact Dual-channel equivalent N/C contact (with
cross-circuit detection)

: Emergency stop button
: Safety door switch
Dual-channel equivalent N/C contact (with
cross-circuit detection)

: Non-contact safety switch Dual-channel equivalent N/C contact 
: Single-beam photoelectric safety
sensor
Dual-channel equivalent N/C contact (with
cross-circuit detection)

4 : Potential free contact Dual-channel complementary N/C / N/O
contact (with cross-circuit detection)

5 : Non-contact safety switch Dual-channel complementary N/C / N/O
contact (with cross-circuit detection and
synchronous time monitoring)

6 : Potential free contact
: Emergency stop button
: Safety door switch
Single-channel N/C contact 
: Potential free contact
: Emergency stop button
: Safety door switch
Dual-channel equivalent N/C contact 
: Electro-sensitive protective
equipment (ESPE)
Electro-sensitive protective equipment
(ESPE) with semiconductor output

: Inductive switch Sensor with semiconductor output (OSSD
output)

: Single-beam photoelectric safety
sensor
Dual-channel equivalent N/C contact 

Table of Contents