80
4 FUNCTIONS
4.11 ENABLE Input (XS0 Terminal)
4.11 ENABLE Input (XS0 Terminal)
ENABLE input (XS0 terminal) is a terminal to enable safety outputs.
Setting method
Connect the XS0 terminal of an FX5-SF-MU4T5 to the same power supply as the plus terminal.
Operation
When the XS0 terminal goes LOW (0 V), the safety outputs Q0 to Q3 always go LOW. The input signals such as a reset and
muting are not detected until the XS0 terminal goes HIGH again.
• When the XS0 terminal goes LOW, the corresponding module does not need to be reset for switching the XS0 terminal to
HIGH again.
• If off delay has been set on Q2 and Q3, the delay time is counted after the XS0 terminal goes LOW.