10 TROUBLESHOOTING
10.2 Checking Errors with an Engineering Tool
121
10
Module information list
The common information of modules such as H/W information including LEDs and switches, and the information specific to
each module can be checked.
Precautions
The information of an FX5-SF-8DI4 is integrated and displayed in the module diagnostics screen of an FX5-SF-MU4T5.
When checking the status of an FX5-SF-8DI4, check the module diagnostic screen of the FX5-SF-MU4T5.
Item Description
Operating status of a safety control Operating status To display the operating status of a safety control.
Whole safety control system System CRC value To display the system CRC value of a safety control.
Internal error To display an error internally occurred in a safety control.
Input cross-circuit error To display the status of an input cross-circuit error in a safety control.
Input process error To display the status of an input process error in a safety control.
Input concurrence error To display the status of an input concurrence error in a safety control.
External device monitoring
connection open
To indicate the connection open status for monitoring external devices for a
safety control.
Status change of a rotary switch To indicate the change status of a safety control rotary switch.
FX5-SF-MU4T5 Input signals I0 to I3 To display the status of inputs from l0 to l3 of an FX5-SF-MU4T5.
Input signal XS0 To display the status of the input XS0 of an FX5-SF-MU4T5.
Input signals X0 to X2 To display the status of inputs from X0 to X2 of an FX5-SF-MU4T5.
Output signals Q0 to Q3 To display the status of outputs from Q0 to Q3 of an FX5-SF-MU4T5.
X0 restart interlock reset request To display the X0 restart interlock reset request status of an FX5-SF-MU4T5.
X1 restart interlock reset request To display the X1 restart interlock reset request status of an FX5-SF-MU4T5.
Muting active status To display the muting status of an FX5-SF-MU4T5.
Bypass active status To display the bypass status of an FX5-SF-MU4T5.
Error code 1 To display an error code of an error occurring in an FX5-SF-MU4T5.
Error code 2
FUNCTION setting To display the setting of the FUNCTION rotary switch on an FX5-SF-MU4T5.
DELAY setting To display the setting of DELAY rotary switch on an FX5-SF-MU4T5.
X0 to X2 settings To display the setting of inputs from X0 to X2 of an FX5-SF-MU4T5.
Safety expansion module n: FX5-SF-
8DI4
Input signals I0 to I7 To display the status of inputs from l0 to l7 of the nth safety expansion module.
Output signals QA and QB To display the status of outputs from QA and QB of the nth safety expansion
module.
Error code 1 To display an error code of an error occurring in the nth safety expansion
module.
Error code 2
INPUT A setting To display the setting of INPUT A rotary switch on the nth safety expansion
module.
INPUT B setting To display the setting of INPUT B rotary switch on the nth safety expansion
module.