APPX
Appendix 5 Buffer Memory
149
A
X1 startup state
The connection information of the X1 terminal at startup is stored.
Buffer memory address
The buffer memory address of this area is as follows.
Status of an X1 terminal
FX5-SF-MU4T5
FX5-SF-8DI4
X2 startup state
The connection information of the X2 terminal at startup is stored.
Buffer memory address
The buffer memory address of this area is as follows.
Status of an X2 terminal
FX5-SF-MU4T5
FX5-SF-8DI4
Buffer memory name Address
1st Module X1 terminal startup state 118
2nd Module X1 terminal startup state 158
3rd Module X1 terminal startup state 198
Bit Name Description
b0 X1 state 00: Open
01: Connected to T0
10: Connected to T1
11: Connected to plus terminal
b1
b2 to b15 Fixed to 0
Bit Name Description
b0 to b15 Fixed to 0
Buffer memory name Address
1st Module X2 terminal startup state 119
2nd Module X2 terminal startup state 159
3rd Module X2 terminal startup state 199
Bit Name Description
b0 X2 state 00: Open
01: Connected to T0
10: Connected to T1
11: Connected to plus terminal
b1
b2 to b15 Fixed to 0
Bit Name Description
b0 to b15 Fixed to 0