4 FUNCTIONS
4.2 Built-In Program Selection Function
49
4
Details of the program 1 for FX5-SF-MU4T5s
The following explains the program when the FUNCTION rotary switch is set to '1'.
For details on the connectable devices and ladder symbols in the program, refer to the following:
Page 48 Connectable devices and ladder symbols
Link a sensor and logic path A or B as follows.
Input for logic path A Assignment Input for logic path B Assignment
Dual-channel equivalent N/C contact, cross-circuit
detection, synchronous time monitoring 1500 ms
T0 to I0
T1 to I1
Dual-channel non-isolated semiconductor + to I2
+ to I3
Dual-channel N/C contact, three-wire + to I2
+ to I3
Four-wire cross-circuit detection (cross-circuit
detection switching mats)
T0 to I0
T1 to I1
Single-channel N/C contact + to I2
+ to I3