6.2 Connections
6.2.1 Pin assignment/Connection diagram + wire colors
MPS-GxxxxxxxAxxxxxxxxxxxxxxxxx: Open cable end
Table 6: Pin assignment for male connector, M8, A-coded, 4-pin
PIN Connection Pin assignment
1 BN + (L+)
2 WH Q2
3 BU - (M)
4 BK Q1
0.08mm
2
AWG 28
MPS-GxxxxxxxCxxxxxxxxxxxxxxxxx / MPS-GxxxxxxxDxxxxxxxxxxxxxxxxx: M8 connection
Table 7: Pin assignment for male connector, M8, A-coded, 4-pin
PIN Connection Pin assignment
1 BN + (L+)
2 WH Q2
3 BU - (M)
4 BK Q1/IO-Link
MPS-GxxxxxxxExxxxxxxxxxxxxxxxx: M12 connection
Table 8: Pin assignment for male connector, M12, A-coded, 4-pin
PIN Connection Pin assignment
1 BN + (L+)
2 WH Q2
3 BU - (M)
4 BK Q1/IO-Link
6.3 Connecting the supply voltage
The sensor must be connected to a voltage supply with the following properties:
•
Supply voltage DC 10V ... 30V (SELV/PELV as per currently valid standards)
•
Electricity source with at least 5W power
Protecting the supply cables
To ensure protection against short-circuits/overload in the customer’s supply cables,
the wire cross-sections used must be appropriately selected and protected.
6 ELECTRICAL INSTALLATION
24
O P E R A T I N G I N S T R U C T I O N S | MPS-G with 2/3 switching points and IO-Link (up to 8 switching points) 8028195/2022-11-30 | SICK
Subject to change without notice