Inductive load
NOTE
Provide an arc-suppression circuit at the digital switching output if an inductive load is
present.
b
Attach a freewheeling diode directly to the load for this purpose.
Table 44: Assignment of placeholders to digital switching outputs
Device CDB620-001
Output A Pin B Pin C Signal D Terminal E
Result 1 13 12 Res 1 20
Result 2 14 13 Res 2 21
Characteristic data of digital switching outputs
Table 45: Characteristic data of the digital switching outputs “Result 1” and “Result 2”
Switching behavior PNP switching to supply voltage V
S
Default settings in the device: no function, logic: not inverted (active
high)
Properties
•
Short-circuit protected + temperature protected
•
Not electrically isolated from V
S
Electrical values 0 V ≤ V
out
≤ V
S
(V
S
−1.5 V) ≤ V
out
≤ V
S
for I
out
≤ 100 mA
NOTE
Assign the functions for the digital switching outputs in the device with a configuration
tool, e.g. the configuration software SOPAS ET.
14.5.10 Wiring digital switching outputs “External output 1” and “External output 2” of the device in the
CDB620-001
Device = RFU62x-104xx (serial variant), RFU62x-101xx (Ethernet variant)
Load (e.g. PLC) 4
GND
V
out
For inductive load: 6
Device 1
Aux
(RS-232)
CDB620-001
CMC600 3
U
IN
*
“External
output A” 2
C
Out B
22
GND
6
Shield
5
Figure 54: Wiring external digital switching outputs “Out 1” and “Out 2” of the device in the connection module CDB620-001