Electrical values 0 V ≤ V
out
≤ V
S
(V
S
−1.5 V) ≤ V
out
≤ V
S
at I
out
≤ 100 mA
NOTE
Assign the functions for the digital switching outputs in the device with a configuration
tool, e.g. the configuration software SOPAS ET.
14.6.10 Wiring digital switching outputs “External output 1” and “External output 2” of the device in the
CDB650-204
Device = RFU62x-101xx (Ethernet variant)
Load (e.g. PLC) 3
GND
V
out
For inductive load: 5
Device 1
Aux
(RS-232)
CDB650-204
CMC600 2
U
IN
*
“External
output A” 6
C
EXT. OUT B
22
GND
6
Shield
4
Figure 66: Wiring external digital switching outputs “EXT. OUT 1” and “EXT. OUT 2” of the device in the connection module
CDB650-204
1
Device
2
The optional parameter cloning module CMC600 is required in the connection module in order to be able to use the
additional external digital switching inputs and outputs of the device
3
Load (e.g. PLC)
4
Output voltage V
out
5
With inductive load: see note
6
Logical “External output” in the device
Inductive load
NOTE
Provide an arc-suppression circuit at the digital switching output if an inductive load is
present.
b
Attach a freewheeling diode directly to the load for this purpose.
Table 59: Assignment of placeholders to digital switching outputs
Device CDB650-204
External output A Signal B Terminal C
1 EXT. OUT 1 23
14 ANNEX
118