Commissioning
3.4 Configuring the drive components
Connection of the SINAMICS S120 to the Technology CPU
Product Information, 09/2011, A5E00480378-04
71
3.4.6 Optimizing the speed controller in the drive
Introduction
The controllers in the drive must be working optimally to ensure that systems are not
susceptible to faults.
There are tools for automatically optimizing the controller in
SINAMICS firmware version V2.5 and S7 Technology V4.1 or later.
The following requirements must be fulfilled to use automatic controller optimization:
The drive may be moved without hitting the mechanical limits
The drive is running in "SERVO" mode.
The motor encoder performs the closed-loop control.
There is an online connection to the relevant drive unit.
The open-loop control is in STOP mode.