Outputs A1, A2, A3, A4
Parameter BACnet object
Selection for A1 A1Sel, STR_VIEW,264
Selection for A2 A2Sel, STR_VIEW,266
Selection for A3 A3Sel, STR_VIEW,268
Selection for A4 A4Sel, STR_VIEW,270
Selection BACnet object R/W Signal type Range
None - - -
Supply air fan speed FanSuSpd R/W 0…10V 0…100%
Exhaust air fan speed FanEhSpd R/W 0…10V 0…100%
Preheating coil electric position PreHclElPos R/W 0…10V 0…100%
Heat exchanger bypass damper position HExgDmpBypPos R/W 0…10V 0…100%
Rotary heat exchanger speed RotHExgSpd R/W 0…10V 0…100%
Heating coil electric position HclElPos R/W 0…10V 0…100%
Heating coil valve position HclVlvPos R/W 0…10V 0…100%
Cooling coil valve position CclVlvPos R/W 0…10V 0…100%
Cooling coil DX evaporator position CclDxPos R/W 0…10V 0…100%
Output Y1
Parameter BACnet object
Selection for Y1 Y1Sel, STR_VIEW,68
Selection BACnet object R/W Signal type Range
None - - -
Preheating coil electric position PreHclElPos R/W PWM Triac
(pulse period
10s)
0…100%
Heating coil electric position HclElPos R/W PWM Triac
(pulse period
10s)
0…100%
A-Alarm indication output AalmIndOut R/W DO Triac NO
B-Alarm indication output BalmIndOut R/W DO Triac NO
Common alarm indication output CmnAlmIndOut R/W DO Triac NO
Operation indication output OpIndOut R/W DO Triac NO
Configuration
Configuring the hardware
4
A6V10733786_en_c 45 | 170