4.5.2.2 Extension module
The following functions can be selected for output signals on the extension module
POS9:
Output Q21
Parameter BACnet object
Selection for Q21 Q21Sel, STR_VIEW,71
Selection BACnet object R/W Signal type Range
None - - -
Outside air damper command DmpOaCmd R/W Relay NO
Fire damper command FdpCmd R/W Relay NO
Preheating coil electric command PreHclElCmd R/W Relay NO
Preheating coil pump command PreHclPuCmd R/W Relay NO
Earth-to-air heat exchanger bypass
damper command
EaHxDmpbCmd R/W Relay NO
Heat exchanger bypass damper command HExgDmpBypCmd R/W Relay NO
Electric heating coil command HclElCmd R/W Relay NO
Heating coil pump command HclPuCmd R/W Relay NO
Cooling coil pump command CclPuCmd R/W Relay NO
Cooling coil DX evaporator command CclDxCmd R/W Relay NO
Dehumidifier free-standing command DhumFrsdCmd R/W Relay NO
A-Alarm indication output AalmIndOut R/W Relay NO
B-Alarm indication output BalmIndOut R/W Relay NO
Common alarm indication output CmnAlmIndOut R/W Relay NO
Operation indication output OpIndOut R/W Relay NO
Output A21
Parameter BACnet object
Selection for A21 A21Sel, STR_VIEW,272
Selection BACnet object R/W Signal type Range
None - - -
Supply air fan speed FanSuSpd R/W 0…10V 0…100%
Exhaust air fan speed FanEhSpd R/W 0…10V 0…100%
Preheating coil electric position PreHclElPos R/W 0…10V 0…100%
Heat exchanger bypass damper position HExgDmpBypPos R/W 0…10V 0…100%
Rotary heat exchanger speed RotHExgSpd R/W 0…10V 0…100%
Heating coil electric position HclElPos R/W 0…10V 0…100%
Heating coil valve position HclVlvPos R/W 0…10V 0…100%
Cooling coil valve position CclVlvPos R/W 0…10V 0…100%
Cooling coil DX evaporator position CclDxPos R/W 0…10V 0…100%
Configuration
Configuring the hardware
4
46 | 170 A6V10733786_en_c