Internal control/status words
Function diagrams
2-551
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Fig. 2-45 2503 – Status word, sequence control
- 2503 -
Function diagram
87654321
FP_2503_97_01.vsd
Internal control/status words
G120 CU230P-2
13.12.2010 V4.4
Status word, sequence control
11
12
13
14
15
PROFIdrive-Bit
10
9
8
7
6
5
4
3
0
1
2
r0899.0
r0899.1
r0899.4
r0899.5
r0899.11
r0899.2
r0899.6
r0899.9
r0899.3
r0899.7
r0899.8
1
&
(1)
2. OFF2
p0845 [C]
(1)
2. OFF3
p0849 [C]
OFF1
OFF2
OFF3
Enable internal
missing or
fault with
this reaction
From the control unit
From the control unit
From the control unit
From the control unit
From the control unit
From the control unit
From the control unit
From the control unit
Bit 9 = 1 --> Ready to exchange process data
From the control unit
The drive is ready to accept data.
Status word sequence control (r0899)
1 = Ready for switching on
1 = Ready for operation (DC link loaded, pulses inhibited)
1 = Operation enabled (drive follows n_set)
1 = Jog active
1 = No coast down active (OFF2 inactive)
1 = No fast stop active (OFF3 inactive)
1 = Switching on inhibited active
1 = Drive ready
1 = Controller enable
1 = Control requested
Reserved
1 = Pulses enabled
Reserved
Reserved
ZSW seq_ctrl
r0899
r0899
Bit No.
<1>
Reserved
Reserved
<1>

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals