EasyManua.ls Logo

Siemens DP/AS-Interface Link 20E

Siemens DP/AS-Interface Link 20E
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Dealing with Problems/Error Displays
135
DP/AS-Interface Link 20E
Release 11/2002
C79000-G8976-C138–04
5.2 Error Displays/Remedying Errors
The following table lists the possible causes of problems during operation of the
DP/AS-i Link 20E module and possible remedies.
Table 5-1
Error
Possible Cause Remedy
BF LED lit (indicates an error on
PROFIBUS)
Connection to the PROFIBUS ma-
ster interrupted.
Check the attachment of the DP
master and DP/AS-i Link 20E mo-
dule to PROFIBUS.
DP master in wrong mode. Check/correct the mode on the
DP master.
Incorrect parameter assignment/
configuration by the PROFIBUS
DP master.
The PROFIBUS address
configured on the DP master does
not match the address of the
DP/AS-i Link 20E module.
Check/correct the configuration of
the DP master.
APF LED lit Power requirements of the AS-i
slaves are too high. Result: Vol-
tage on the AS-i cable too low.
Check the power requirements of
the AS-i slaves. If necessary,
supply the AS-i slaves with an
external voltage.
PWR LED not lit The AS-i power supply unit is not
connected or is defective.
Check the connection of the AS-i
power supply unit and if
necessary replace it.
Short circuit on the AS-i cable Check the AS-i cable and the
connected AS-i slaves.
SF lights up without pressing the
SET button.
The DP/AS-i Link 20E module si-
gnals diagnostic information to the
DP master.
Causes: Parameter assignment/
configuration error on PROFIBUS,
configuration error on the AS-In-
terface (for example slave failed)
or AS-i Power Fail.
Check the “CER”, ”APF” LEDs.
Evaluate the bits in the slave dia-
gnostic information to identify the
error in greater detail.
SF is lit when the SET button is
pressed.
A slave with address 0 exists
when there is a change to the pro-
tected mode.
Remove the slave with address 0
from the AS-i cable.
CER LED is permanently lit. The DP/AS-i Link 20E module has
not yet been configured.
Configure the DP/AS-i Link 20E
module using the SET button on
the front panel.
A configured AS-i slave has failed
(evaluate the slave display).
Replace the defective AS-i slave
or reconfigure the DP/AS-
i Link 20E module if the AS-i slave
is not required.
An unconfigured slave was con-
nected to the AS-i cable.
Remove the AS-i slave or
reconfigure the DP/AS-i Link 20E
module.

Table of Contents

Related product manuals