EasyManua.ls Logo

Siemens DP/AS-Interface Link 20E - Get_Extended_Actual_Configuration

Siemens DP/AS-Interface Link 20E
160 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Using the Command Interface
90
DP/AS-Interface Link 20E
Release 11/2002
C79000-G8976-C138–04
3.3.9 Get_Extended_Actual_Configuration
Purpose of the Command
With this call, the following configuration data of an addressed AS-i slave obtained
by the AS-i master on the AS-Interface are read.
S I/O configuration
S ID code
S Extended ID1 code
S Extended ID2 code
The configuration data are specified by the manufacturer of the AS-i slave. The
meaning of the configuration data is described in /2/.
Structure of the Job Data in the Send Buffer
Byte Meaning
0 Command number 28
H
1 Slave address
Structure of the Response Data in the Receive Buffer
Byte Meaning
Bit 7 Bit 4 Bit 3 Bit 0
0 ID code I/O configuration
1 Extended ID1 code Extended ID2 code
2 reserved
3 reserved

Table of Contents