EasyManua.ls Logo

Siemens DP/AS-Interface Link 20E

Siemens DP/AS-Interface Link 20E
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Using the Command Interface
82
DP/AS-Interface Link 20E
Release 11/2002
C79000-G8976-C138–04
3.3.1 Set_Permanent_Parameter
Purpose
With this call, a parameter value for the specified AS-i slave is configured on the
DP/AS-i Link 20E. The value is stored permanently in the EEPROM of the
DP/AS-i Link 20E.
The configured parameter is not transferred immediately by the DP/AS-i Link 20E
to the AS-i slave. The configured parameter value is only transferred when the
AS-i slave is activated after turning on the power supply on the DP/AS-i Link 20E.
This call is not permitted for AS-i slaves that comply with the AS-i slave standard
profile 7.4. For these AS-i slaves, the AS-i master handles the AS-i slave
parameter assignment itself. In this case, the configured parameters are always
set to F
H
.
Note
If you use CPUs from the SIMATIC S7 system as the PROFIBUS DP master, then
dependent on the configuration in STEP 7, these may send a complete AS-i slave
configuration to the DP/AS-i Link 20E during the DP startup. Use of the call
described here is then generally unnecessary.
Structure of the Job Data in the Send Buffer
Byte Meaning
Bit 7 Bit 4 Bit 3 Bit 0
0 Command number: 00
H
1 Slave address
2 irrelevant Parameter

Table of Contents

Related product manuals