EasyManua.ls Logo

Siemens DP/AS-Interface Link 20E

Siemens DP/AS-Interface Link 20E
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Data Exchange Between the DP Master and AS-i Slave
51
DP/AS-Interface Link 20E
Release 11/2002
C79000-G8976-C138–04
Example of a Configuration
Figure 2-2 shows an example of the PROFIBUS DP master addressing four AS-i
slaves. In the DP master, the start addresses m = 0 are used for the I/O data.
The bits relevant for the user program (existing AS-i slaves) are shown on a gray
background. The bits shown on a white background are irrelevant for the user
program since no AS-i slaves are assigned here.
DP master
32
Input bytes
0
4
56
7
0
1
234
567
1
.
.
.
31
.
.
.
4 I module
Slave no. 2 Slave no. 3 Slave no. 4
Slave no. 31B
AS-i slaves
4 I module 4 I/3 O module2 I/2 O module 4 O module
2
31
0
0
1
2
slave 1
slave 1
slave 2 slave 3
Slave 30B
slave 4
slave 5
slave 2 slave 3
slave 4
slave 5
Slave 30B
Slave 31B
Bit 0
Bit 1Bit 2
Bit 3
Bit 0
Bit 0
Bit 0
Bit 0
Bit 0
Bit 0
Bit 0 Bit 0
Bit 0
Bit 0
Bit 0
Bit 0
Bit 1
Bit 1
Bit 1
Bit 1
Bit 1
Bit 1
Bit 1
Bit 1
Bit 1
Bit 1
Bit 1
Bit 1
Bit 3
Bit 2
Bit 2Bit 2
Bit 2
Bit 2
Bit 2
Bit 2
Bit 2
Bit 2
Bit 2
Bit 2
Bit 2
Bit 2
Bit 3
Bit 3
Bit 3
Bit 3
Bit 3
Bit 3
Bit 2
Bit 3
Bit 3
Bit 3
Bit 3
Bit 3
Bit 3
Bit 3 Bit 1 Bit 0
Bit 1
Bit 0
Output bytes
32
Bit 2
Slave 31B
Bit 0
Bit 1
Bit 3
Figure 2-2
In the figure above, for example, the 2I/2O module (AS-i slave number 3 with two
inputs and two outputs) occupies bits 0 and 1 in input byte 1 and bits 2 and 3 in
output byte 1.
The assignment of the AS-i terminals of the AS-i bus modules to the data bits of
the input/output bytes is shown below based on the example of slave number 3:
1 0 Bit no.
Input byte 1
Terminal 1 on the AS-i bus
module
Terminal 2 on the AS-i bus
module

Table of Contents

Related product manuals