EasyManua.ls Logo

Siemens et 200sp - Page 105

Siemens et 200sp
173 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuring/address space
4.5 Frequency output mode
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
104 Manual, 05/2019, A5E35061186-AB
Byte
offset
relative
to start
address
Channel
0/1
↓ ↓
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
9 21 Reserved SET_DQB SET_DQA Reserved TM_
CTRL_DQ
SW_
ENABLE
10 22 Reserved RES_
ERROR
11
23
Reserved
Note
Channel 1 is only available in two
-channel operation of the module.
Control bit/value
Explanations
OUTPUT_VALUE You specify the frequency with this value.
Value range:
Frequency in Hz, when High-speed output is deactivated: 0.02 to 10000
D
Frequency in Hz, when high-speed output is activated: 0.02 to 100000
D
If the low limit or the high limit is violated, the feedback bit ERR_OUT_VAL is set and the last
valid frequency is used.
SLOT You specify the load value with this value.
Value range:
On delay in μs: 0 to 85000000
D
You specify whether to apply a change once or cyclically with MODE_SLOT.
Invalid values trigger setting of feedback bit ERR_LD (when MODE_SLOT = 0) or
ERR_SLOT_VAL (when MODE_SLOT = 1).
MODE_SLOT You specify whether you want to apply a change in SLOT once or cyclically with this bit.
0 means: As soon as you write the value 2
D
in the corresponding output byte, the value from
SLOT is applied once and kept until the next change. A change via SLOT takes effect at the
next output sequence. After a restart of the module, the value is overwritten with the value set
in the hardware configuration.
1 means: When you write the value 18
D
in the corresponding output byte, the current value
from SLOT in each case is applied cyclically. A change via SLOT takes effect at the next output
sequence.
LD_SLOT You specify the meaning of the value in SLOT with this load request:
0000
B
means: No action, idle
0010
B
means: On delay in μs
Values not listed are invalid and trigger setting of feedback bit ERR_LD (when MODE_SLOT =
0) or ERR_SLOT_VAL (when MODE_SLOT = 1).
SET_DQA
You use this bit to set digital output DQn.A when TM_CTRL_DQ and SET_DQB are set to 0.
SET_DQB
You use this bit to set digital output DQn.B when TM_CTRL_DQ and SET_DQA are set to 0.

Table of Contents

Other manuals for Siemens et 200sp

Related product manuals