4.9.5 Parameter
High-speed output (0.1 A)
Use this parameter to specify whether or not the respective digital output works as a fast
push-pull switch.
Activated The digital outputs work as fast push-pull switches and each can carry a
rated load current of 0.1 A. A push-pull switch is alternately switched to
DC 24 V and ground. This makes for very fast edges.
Disabled
(default)
The digital outputs work as fast push-pull switches and each can carry a
rated load current of 2 A.
Note
Channel configuration
You can only select this parameter with the channel configuration "2 channels (2 A)".
enable this parameter in the operating modes "PWM with DC motor" and "Pulse
width modulation PWM" with current control.
Function DI
By configuring a digital input, you specify which functions the digital input triggers at
switching.
You can select from the following options:
Input
(pre-selected)
No function is assigned to the respective digital input. The signal status of
the digital input can be read by the CPU by means of the feedback inter-
HW enable The respective digital input is used as enable input for the output se-
Limit switch The respective digital input is used as external limit switch for a DC motor
in the "PWM with DC motor" mode.