Configuring/address space
4.9 Explanation of parameters
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
134 Manual, 05/2019, A5E35061186-AB
Input delay
This parameter can be used to suppress signal noise at the digital inputs of a channel.
Changes to the signal are only detected if they remain stable for longer than the configured
input delay time.
You can select from the following input delays:
None
(input delay of 4 μs, minimum pulse width of 3 μs)
0.05 ms
0.1 ms (default)
0.4 ms
0.8 ms
1.6 ms
3.2 ms
12.8 ms
20 ms
Note
If you select the "None" or "0.05
ms" option, you have to use shielded cables for connection
of the digital inputs.
Output format
Use this parameter to specify the format or the value range with which the duty cycle or the
current setpoint is evaluated:
Output format
Value range
S7 analog output "PWM with DC motor" mode:
27648 ... 27648
Other operating mode:
0 ... 27648
("27648" corresponds to 100% of Reference value current)
1/100
(default)
0 ... 100
1/1000
0 ... 1000
1/10000
0 ... 10000
Note
In "Frequency output" mode, "1
Hz" is selected as output format and cannot be changed.
In "PWM with DC motor" mode, "S7 analog output" is selected as output format and
cannot
be changed.