4.5 Frequency output mode
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
98 Manual, 05/2019, A5E35061186-AB
4.5.1.4 High-speed output
The high-speed output function enables an output frequency of a maximum of 100 kHz with
an output current of a maximum of 100 mA. A high-speed output generates very steep
edges. The high-speed output generates signals at a higher frequency, but provides a lower
maximum load current. The high-speed output is only available in two-channel operation.
The following table presents the value range of the pulse duration and frequency depending
on whether or not the high-speed output function is activated:
Minimum value
Maximum value
High-speed output
deactivated
High-speed output
activated
High-speed out-
put deactivated
High-speed
output activated
Pulse duration
10 μs
1,5 μs
85000000 μs (= 85 s)
Frequency
0,02 Hz
10 kHz
100 kHz