Configuring/address space
4.6 PWM with DC motor motor
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 05/2019, A5E35061186-AB
121
ERR_LD This bit indicates that the value in SLOT or LD_SLOT (when MODE_SLOT = 0) is invalid and was
not accepted.
The bit is reset once you have acknowledged the error with RES_ERROR.
ERR_24V This bit indicates a short-circuit or an overload at output 24VDC If you have enabled diagnostic
interrupts, the diagnostic interrupt "Short circuit / overload of the sensor supply voltage" is triggered
when this error occurs.
The bit is reset once you have acknowledged the error with RES_ERROR.
ERR_PWR This bit indicates that supply voltage L+ is too low. If you have enabled the diagnostic interrupts,
the diagnostic interrupt "Supply voltage fault" is triggered when an error occurs.
As soon as supply voltage L+ is sufficiently high again, ERR_PWR is automatically reset.
The bit is not set if no supply voltage is present.
STS_SW_ENABLE This bit indicates the status of the SW enable.
• 0 means: SW enable not active
• 1 means: SW enable active
STS_READY This bit indicates that the module is supplying valid user data. The module is started and config-
STS_LD_SLOT A status change (toggling) of this bit indicates that the LD_SLOT load request was detected and
executed (when MODE_SLOT = 0).
This bit indicates the status of the digital input DIn.0.
This bit indicates the status of the digital output DQn.A.
This bit indicates the status of the digital output DQn.B.
This bit indicates that an output sequence is active.
Reserved bits are set to 0.