Connecting
3.1 Terminal assignment and schematic circuit diagram
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 05/2019, A5E35061186-AB
19
Terminal assignment of the BaseUnit
The table below shows the terminal assignment of the BaseUnit BU20-P12+A0+4B.
Table 3- 1 Terminal assignment of the BaseUnit BU20-P12+A0+4B
Channel 0
DI0.0 3 4 DI1.0 Channel 1
Channel 0
Ground for digital inputs
M 5 6 M Channel 1
Ground for digital inputs
Channel 0
Ground for digital outputs
M 7 8 M Channel 1
Ground for digital inputs
Channel 0
DQ0.A 9 10 DQ1.A Channel 1
Channel 0
DQ0.B 11 12 DQ1.B Channel 1
24 V DC supply voltage L+ 13
14
M Ground for supply voltage
L+ 15
(2L)
16
(2N)
M
Cable shielding
You must ground the shields of the cables between sensors and the technology module and
connect them to the DIN rail or the ground connection of the central power supply of the
plant.