EasyManua.ls Logo

Siemens et 200sp - Page 29

Siemens et 200sp
173 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuring/address space
4.1 Pulse output (single pulse) mode
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
28 Manual, 05/2019, A5E35061186-AB
Parameters of the TM Pulse 2x24V in "Pulse output" mode
The default settings of the parameters are shown in bold in the "Value range" column.
Table 4- 2 Adjustable parameters
Parameter
Value range
Scope
Channel configuration
1
2 channels (2 A)
1 channel (4 A)
Module
Reaction to CPU STOP
Output substitute value
Continue operation
Channel
Substitute value for DQA
0
1
Channel
Substitute value for DQB
0
1
Channel
Group diagnostics
Deactivated
Activated
Channel
Diagnostics DQA
Deactivated
Activated
Channel
Diagnostics DQB
Deactivated
Activated
Channel
High-speed output (0.1 A)
Deactivated
Activated
Channel
Function DI
Input
HW enable
Channel
Input delay for digital inputs
None
0.05 ms
0.1 ms
0.4 ms
0.8 ms
1.6 ms
3.2 ms
12.8 ms
20 ms
Channel
Output format
S7 analog output
1/100
1/1000
1/10000
Channel
On delay for pulse output
0
...85000000 μs
Channel
1
When configuring with HSP for STEP 7 or with a GSD file, you define the channel configuration by
the selection of the module name.
Note
PROFIBUS GSD configuration
When configuring with a PROFIBUS GSD file, the possible parameter assignments are not
available. The parameters are preassigned in the module with the default setting. Set the
"Pulse output" mode and the further parameters in the user program
using data record 128.

Table of Contents

Other manuals for Siemens et 200sp

Related product manuals