Operation
Specifying the operation mode for Cerberus Mobile
5
100 | 184
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015
12
15
5.23 Specifying the operation mode for Cerberus Mobile
Specification of operation mode on the 'Station'
The '
Cerberus Mobile
' element must be configured manually in
Cerberus
-
Engineering-Tool' for a 'Station'.
You can configure a permanent operation mode for '
Cerberus Mobile
' i
n
'Cerberus-Engineering-Tool'. If 'Permanent Cerberus Mobile access' is
configured, you do not need to define the operation mode on the 'Station'.
1. Select 'Main menu' > 'Topology'.
2. Select the 'Hardware tree' subtree.
3. Navigate to 'Station' > 'Mobile'.
4. Press the 'MoreOptions' softkey.
5. Select 'Execute Commands' and confirm with <ok>.
The 'Select command' window is open.
6. Select the 'Enable full access' or 'Enable view access' command and confirm
with <ok>.
The operation mode for 'Cerberus Mobile' is now specified.
Deactivation of operation mode on the 'Station'
If you have permanently configured the operation mode in '
Cerberus
-
Engineering
-
Tool', you must deactivate the operation mode in 'Cerberus-Engineering-Tool'.
Proceed as for 'Specification of operation mode on the 'Station'' and select the
Disable access' command in the 'Select command' window.
5.24 Enabling a smartphone
You can use
Cerberus Mobile
in a fire detection installation with networked
'Stations' to gain global 'Visibility'. Just one license key is needed for this per
network in the 'Station' to which 'Cerberus Mobile' is connected.
You will find more information about license keys in document A6V10210362.
See chapter 'Applicable documents'.
To enable a smartphone at the 'Station', proceed as follows:
ϖ You have specified the Visibility for smartphones in 'Cerberus-Engineering-
Tool'.
ϖ You have specified the operation mode for Cerberus Mobile at the 'Station'.
ϖ You have established a connection with the 'Station' on your smartphone.
ϖ You have installed 'Cerberus Mobile' on your smartphone.
ϖ You have started 'Cerberus Mobile' on your smartphone.
ϖ The 'New client found' message is displayed. The IMEI number of the
smartphone is displayed for identification purposes. For more information, see
the example display at the end of this chapter.