System description
Intervention concept (IC)
9
164 | 184
Building Technologies
A6V10211076_
i_en_
--
Fire Safety
2015
12
15
The 'Intervention Concept' ('IC') is an integral part of the fire control panel and
takes into account the interaction of the operating personnel. The 'Intervention
Concept' can be used to define an intervention process which is initiated should an
event occur or once a particular delay time has lapsed.
For each of the following event categories the behavior can be defined separately:
'Fault'
'Isolation'
Test
'Technical message'
'Activation'
'Information'
The 'Intervention Concept' has two independent, parallel intervention processes:
Attendance check (t1)
Intervention monitoring (ts)
The intervention process can be configured according to the 'Manned
operation'/'Unmanned operation' operation mode.
A triggered intervention process (t1 and/or ts running) is not restarted when a
'Fault' of the same category occurs for a second time.