Operation
Switching off / Switching on
5
52 | 184
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015
12
15
Select command
All zones ON
All zones OFF/timer
MCP zones OFF
Non-MCP zones ON
Non-MCP zones OFF
(2)
(3)
(4)
(5)
(6)
κ WARNING! System parts that have been switched off make it impossible to
acquire and process alarms or faults! Select 'All zones OFF/timer' and confirm
with <ok>.
Enter duration
05:00
(hh:mm)
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
κ Enter the duration: e.g., 5 hours.
You receive a command response.
Execute command
All zones OFF/timer
Command executed
The adjustable duration may be limited, depending on the country.
The duration of the 'Isolation' may be changed subsequently.
An unlimited 'Isolation' can be temporarily limited, and vice versa.