FS-100 Installation & Operation Manual
P/N 315-699461 9
GENERAL SPECIFICATIONS
Operating specifications for the FS-100 are as follows:
Environmental
• Operating temperature
32 - 120°F (0 - 49°C)
• Relative humidity
Up to 85% @ 86°F (30°C)
Primary Supply
• Primary Input Voltage: 120 VAC (60 Hz) nominal (FS-100-120)
• Maximum primary input current: 1.3A at 120 VAC
Secondary and Trouble Power Supply
• 24 volt lead-acid battery set:
• Maximum Charge Voltage: 27.8 VDC
• Maximum Charge Current: 1.0 A
• Maximum Input Current: 3.5A
• Battery capacity: 7-38 A.H. (over 7 A.H. requires separate enclosure)
Auxiliary Power Outputs
• Current:
0.5 amp maximum available for auxiliary power outputs, RS485 circuit and option boards
0.4 amp maximum per power output
• Non-Resettable Power Outputs
Power limited
Voltage: 24 VDC nominal
Ripple: 1.5 VAC maximum
• Resettable Power Output
Power limited
Voltage: 24 VDC nominal
Ripple: 1.5 VAC maximum
Status Relays
• Includes alarm, supervisory and trouble relays.
• Contact Rating:
1 A, 28 VDC maximum, resistive
• Form “C” Contact
Notification Appliance Circuits
• Four Class A, Style Z/Class B, Style Y circuits
• Power limited
• Supervised
• Maximum Standby Current: 3.4mA
• Alarm Voltage: 24 VDC nominal
• Maximum Alarm Current per circuit: 1.5 A
• Total Maximum Alarm Current (all circuits): 2.5 A
• Maximum Ripple: 16 VAC
• Maximum Loop Drop Voltage: 1.0 VDC