FS-100 Installation & Operation Manual
P/N 315-699461 9
GENERAL SPECIFICATIONS
Operating specifications for the FS-100 are as follows:
Environmental
Operating temperature
32 - 120°F (0 - 49°C)
Relative humidity
Up to 85% @ 86°F (30°C)
Primary Supply
Primary Input Voltage: 120 VAC (60 Hz) nominal (FS-100-120)
Maximum primary input current: 1.3A at 120 VAC
Secondary and Trouble Power Supply
24 volt lead-acid battery set:
Maximum Charge Voltage: 27.8 VDC
Maximum Charge Current: 1.0 A
Maximum Input Current: 3.5A
Battery capacity: 7-38 A.H. (over 7 A.H. requires separate enclosure)
Auxiliary Power Outputs
Current:
0.5 amp maximum available for auxiliary power outputs, RS485 circuit and option boards
0.4 amp maximum per power output
Non-Resettable Power Outputs
Power limited
Voltage: 24 VDC nominal
Ripple: 1.5 VAC maximum
Resettable Power Output
Power limited
Voltage: 24 VDC nominal
Ripple: 1.5 VAC maximum
Status Relays
Includes alarm, supervisory and trouble relays.
Contact Rating:
1 A, 28 VDC maximum, resistive
Form “C” Contact
Notification Appliance Circuits
Four Class A, Style Z/Class B, Style Y circuits
Power limited
Supervised
Maximum Standby Current: 3.4mA
Alarm Voltage: 24 VDC nominal
Maximum Alarm Current per circuit: 1.5 A
Total Maximum Alarm Current (all circuits): 2.5 A
Maximum Ripple: 16 VAC
Maximum Loop Drop Voltage: 1.0 VDC
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FireSeeker FS-100 and is the answer not in the manual?

Siemens FireSeeker FS-100 Specifications

General IconGeneral
BrandSiemens
ModelFireSeeker FS-100
CategoryFire Alarms
LanguageEnglish

Related product manuals