FS-100 Installation & Operation Manual
P/N 315-699461 34
Addressable Modules
Each addressable module uses an address between 01 and 60 on the addressable device circuit. All
module addresses are programmed into the module using the FS-FPI Programmer / Tester. When
installed, the module is regularly scanned by the control unit and checked for its current circuit status.
The control unit will interpret and respond to the analog data as programmed. Each time the module is
scanned the integral green visible LEDs will flash. In the event of an alarm condition the red LEDs will
flash at a faster rate.
Transmit & Receive Interface Modules
The FS-TRI-S monitor module provides a single Style "B" (2-wire) initiating circuit for normally open dry
contact fire alarm and supervisory (tamper) devices. The FS-TRI-S is designed to mount directly inside a
4" square junction box, and has screw terminals for all field connections. The FS-TRI-S may be used to
monitor manual stations, waterflow switches, tamper (supervisory) switches or other dry, normally open
contact initiation devices. It uses a single module address between 01 and 60.
The FS-TRI-M monitor module functions exactly as the FS-TRI-S, except that it is smaller than the FS-
TRI-S, and it uses flying leads for field connections. The FS-TRI-M’s small size and light weight design
allows it to be installed inside a single gang box, or behind a device being monitored without being rigidly
mounted.
The FS-TRI-D monitor module is similar to the FS-TRI-S, except that it provides two Style ‘B” initiating
circuits for normally opened dry contact fire alarm and supervisory (tamper) devices. The FS-TRI-D uses
two consecutive module addresses between 01 and 60 on the addressable device circuit.
The FS-TRI-R monitor module is similar to the FS-TRI-S, except that it also provides a programmable
remote relay which operates a Form C contact within the module. Both the initiating circuit and the relay
output share the same address.
FS-CZM Conventional Zone Module
The FS-CZM addressable conventional zone module allows the addressable device circuit to interface
and monitor two-wire conventional smoke detectors or normally open contact initiation devices. All two-
wire detectors being monitored must be UL compatible with the module. The FS-CZM communicates the
status of a single zone of conventional detectors to the control panel via the addressable device circuit.
When the panel scans the module, it transmits the status of one zone of two-wire detectors to the control
unit. Status conditions are reported as normal, open, or alarm. The FS-CZM uses a single module
address between 01 and 60 on the addressable device circuit.
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FireSeeker FS-100 and is the answer not in the manual?

Siemens FireSeeker FS-100 Specifications

General IconGeneral
BrandSiemens
ModelFireSeeker FS-100
CategoryFire Alarms
LanguageEnglish

Related product manuals