Setting the new value
Pre-purgeTimeGas
Cu r r : 12 . 6s
New :30s
b) As soon as the basic unit has handled the parameter settings, the new value appears
on line «Curr». The user has to make certain that the 2 values are identical (safety
test of display).
Pre-purgeTimeGas
Cu r r : 30s
New :30s
The user can return to the next higher menu level by pressing ESC.
To make the addressing, the actuator must be opened. A button and an LED are located
behind the actuator’s removable plastic cover.
In connection with addressing with the help of the AZL5…, the button is used to define
the address of an actuator.
When commissioning the plant, the actuators are in their addressing mode.
To indicate this, the LED is steady on. If the LED is not steady on, refer to «Reset»
below.
To make the addressing, the following menu is required on the AZL5…:
«Params & Display» Æ «Actuators» Æ «Addressing»
This menu contains the choice of actuators to be addressed (e.g. the air actuator). By
appropriately positioning the pointer and then pressing ENTER, the user can select the
required actuator function.
Address assignment is started by pressing ENTER. After a short period of time, the user
will be prompted to press the button on the actuator to be addressed.
The AZL5… confirms the successful address assignment. To be sure, the address of
the actuator can be checked against the blink code which now appears.
This procedure can be repeated for other actuators used by the system, but the AZL5…
does not allow double assignments. In that case, a display tells the user that an
appropriate actuator is already used by the system.
Addressing the actuators
(function assignment)

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals