EasyManua.ls Logo

Siemens LMV5 Series - Input 4: TEMP, Pt1000; LG-Ni 1000 X60

Siemens LMV5 Series
278 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
79/278
Siemens Building Technologies Basic Documentation LMV51... CC1P7550en
HVAC Products 6 Temperature or pressure controller (internal load controller LC) 01.10.2003
2-wire circuit. Line balancing is not required if the resistances of the measuring leads
are small compared to the sensor's resistance.
The TL function is active.
The sensors to be used are QAE22.5A and QAE21.1.
Start of measuring range: 0 °C or 32 °F
End of measuring range: 150 °C or 302 °F
or (can be parameterized)
400 °C or 752 °F
Parameter: MeasureRange PtNi
Input 4: TEMP,
Pt1000 / LG-Ni 1000
X60