Siemens Building Technologies Basic Documentation LMV51... CC1P7550en
HVAC Products 8 Commissioning instructions for the LMV5... system 01.10.2003
The integrated temperature limiter observes a separate temperature limit.
(for details «Integrated temperature limiter function»).
After the switch-off point in °C for the temperature limiter has been entered, the relative
switch-on point in % will be given.
Example: TW_Threshold_Off: 80 °C
TW_SwiDiff_On -10 % ( = 8 K)
Temperature limitation on at 72 °C
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6
Params & Display
LoadController
TempLimiter
TL_Thresh_Off
TL_SD_On
Or
SystemConfig
TempLimiter
TL_Thresh_Off
TL_SD_On
2 boiler setpoints can be adjusted which, however, may not lie above the current limit
value of the temperature limiter function ( «Setpoints»).
Changeover from setpoint W1 to setpoint W2 is accomplished by means of an external,
potential-free contact at input 3.
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6
Params & Display
LoadController
ControllerParam
Setpoint W1
Setpoint W2
Or
Operation
BoilerSetpoint
Setpoint W1
Setpoint W2
Temperature limiter
function
Boiler setpoints
W1 and W2