EasyManua.ls Logo

Siemens LMV5 Series - Page 172

Siemens LMV5 Series
278 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
172/278
Siemens Building Technologies Basic Documentation LMV51... CC1P7550en
HVAC Products 10 Description of the connection terminals 01.10.2003
10 Description of the connection terminals
Terminal
designa-
tion
Connection symbol
Input
Output
Description Electrical rating
PIN1 x Fan motor contactor AC 230 V +10 % / -15 %, 50...60 Hz,
1 A, cos
ϕ 0.4
X3-01
PIN2
x Alarm AC 230 V +10 % / -15 %, 50...60 Hz,
1 A, cos
ϕ 0.4
PIN1 x Air pressure switch (LP) AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
X3-02
PIN2
x Power signal for air pressure switch
(LP)
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
PIN1 x End switch burner flange AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 5 A
X3-03
PIN2
x Power signal for end switch burner
flange
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 5 A
PIN1 x Safety loop AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 5 A
PIN2 x Power signal for safety loop AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 5 A
PIN3 x Protective earth (PE)
PIN4 x Neutral conductor (N)
X3-04
PIN5
x Live conductor (L) AC 230 V +10 % / -15 %, 50...60 Hz,
fuse 6.3 AT
(DIN EN 60 127 2 / 5)
Fuel selection “internal” if pin 1-2 is not
used
PIN1 x Fuel selection gas AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
PIN2 x Fuel selection oil AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
PIN3 x Fan contactor contact (FCC) or FGR-
PS
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
X4-01
PIN4
x Reset / manual lockout AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
PIN1 x Protective earth (PE)
PIN2 x Neutral conductor (N)
X4-02
PIN3
x Ignition AC 230 V +10 % / -15 %, 50...60 Hz,
2 A, cos
ϕ 0.2
PIN1 x Protective earth (PE)
PIN2 x Neutral conductor (N)
X4-03
PIN3
x Start signal or PS relief (APS test valve) AC 230 V +10 % / -15 %, 50...60 Hz,
0.5 A, cos
ϕ 0.4
PIN1 x Protective earth (PE)
PIN2 x Pressure switch min-oil (DWmin-oil) AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
X5-01
PIN3
x Power signal for pressure switch-min-oil
(DWmin-oil)
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
PIN1 x Protective earth (PE)
PIN2 x Pressure switch-max-oil (DWmax-oil) AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
X5-02
PIN3
x Power signal for pressure switch-max-
oil (DWmax-oil)
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
PIN1 x Controller (ON / OFF) AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
PIN2 x Controller closes / stage 3 AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
PIN3 x Controller opens / stage 3 AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
X5-03
PIN4
x Power signal for control of controller AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA