EasyManua.ls Logo

Siemens LMV5 Series - Page 187

Siemens LMV5 Series
278 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
187/278
Siemens Building Technologies Basic Documentation LMV51... CC1P7550en
HVAC Products 13 Technical data 01.10.2003
13 Technical data
13.1 LMV5... and AZL5...
Mains voltage AC 230 V -15 % / +10 %
Transformer AGG5.220
- Primary side
- Secondary side
AC 230 V
AC 12 V
2 x AC 12 V
Mains frequency 50...60 Hz ±6 %
Power consumption (typically) < 30 W
Safety class I with parts according to II and III as per
DIN EN 60 730-1
Transport
DIN EN 60 721-3-2
Climatic conditions class 2K2
Mechanical conditions class 2M2
Temperature range -20...+70 °C
Humidity < 95 % r.F.
Operation
DIN EN 60 721-3-3
Climatic conditions class 3K5
Mechanical conditions class 3M2
Temperature range (incl. mounting. plate) -20...+60 °C
Humidity < 95 % r.h.
Condensation, formation of ice and ingress of water are not permitted!
Operating voltage AC 24 V -15 % / +10 %
Power consumption (typically) < 5 W
Degree of protection of housing
– Rear
– Front
IP00, IEC 529
IP54, IEC 529 (when built in)
Safety class I with parts according to II and III as per
DIN EN 60 730-1
Transport
DIN EN 60 721-3-2
Climatic conditions Class 2K3
Mechanical conditions Class 2M2
Temperature range -20...+60 °C
Humidity < 95 % r.F.
Operation
DIN EN 60 721-3-3
Climatic conditions Class 3K3
Mechanical conditions Class 3M2
Temperature range (incl. mounting plate) -20...+60 °C
Humidity < 95 % r.F.
Condensation, formation of ice and ingress of water are not permitted!
Basic unit LMV5...
Environmental
conditions LMV5...
A
ZL...
Environmental
conditions AZL5...

Table of Contents