10.4 Derating Factors 
10.4.1 Derating with Temperature 
Operation of the inverter outside its recommended ambient operating temperature 
would normally cause the inverter to trip with an overtemperature fault code. To 
avoid such tripping, the inverter automatically reduces its switching frequency (e.g. 
from 16 kHz to 8 kHz), thus reducing the temperature of the heatsink, enabling the 
application to continue running trip free. Should the load or ambient temperature 
then reduce, the inverter will first check to see if it is safe to increase the switching 
frequency again and if considered safe will then do so. 
80
60
40
0
20
100
-10 0 7010 20 30 40 50 60
°C
%
Rated Output Current
 
Figure 10-16  Reduktionsfaktoren durch die Umgebungstemperatur 
10.4.2 Derating with Altitude 
 Figure 10-17 shows the permissible rated input voltage and output current for 
inverter installations from 500 m to 4000 m above sea level. 
Input voltage
Permissible rated input voltage as a
percentage of the nominal voltage
100
90
80
60
70
1000 2000 3000 4000
500 500
100
90
80
60
70
1000 2000 3000 4000
Permissible rated output current as a
percentage of the nominal current
Rated output current
Installation altitude in meters above sea level
 
Figure 10-17  Derating with Altitude