3  Commissioning  Issue 03/01 
  MICROMASTER 411 & COMBIMASTER 411    Operating Instructions  
48 
6SE6400-5CA00-0BP0  
 
Figure 3-4  Control Circuit Jumpers 
Table 3-3  Control Circuit Jumper Settings 
Jumper  Jumper Fitted  Jumper Removed 
Pot = Run  P0700 = 2 
P0705 = 1 (motor potentiometer) 
P1210 = 6  automatic restart 
P0700 = 2 
P0701 = 1 
P1210 = 1 
24 AIN  No software effect  No software effect 
DC Brake  Uses the jumper settings for the ramp settings by the 
duration of the direct current braking, to be calculated as 
follows. 
Duration of direct current braking = 
 
 
 
If the drive is quicker to  come to a standstill because of the 
load conditions, the direct current braking still remains 
active fo the calculated time time. 
Otherwise the value is held in P1233 (duration of the diret 
current braking) 
P1233 = 0 
Fan/Pump: M~n2  P1300 = 2 (fan curve/quadratic vf)  P1300 = 0 (linear vf) 
50/60 Hz  Rated Motor Frequency = 60 Hz  Rated Motor Frequency = 50 Hz 
Control Jumpers 
In Table 3-4 the behaviour of the Control Jumpers are explained. 
Table 3-4  Control Circuit Jumper Behaviour 
Status before action(s)  Action(s)  Reaction(s) of the inverter 
Jumper not fitted    Power down 
  Fit jumper(s) 
  Power up 
Parameters influenced by jumper will have jumper default 
values 
Jumper fitted    Cycle power  Parameters influenced by jumper are not changed 
Jumper fitted    Power down 
  Remove jumper 
  Power up 
Parameters influenced by jumper will have “jumper 
removed“ default values (normally factory default) 
Jumper not fitted    Cycle power  Parameters influenced by jumper are not changed 
 
P0305 (nominal motor current) 
r0207 (nominal inverter current) 
P1121 (deceleration time) 
*