3  Commissioning  Issue 03/01 
  MICROMASTER 411 & COMBIMASTER 411    Operating Instructions  
54 
6SE6400-5CA00-0BP0  
Flow chart Quick Commissioning (Level 1 Only) 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
1) 
related parameters – please refer to motor rating plate drawing.  
2)
  Denotes parameters that contain more detailed lists of possible settings for use in specific 
applications. Please refer to the Parameter List. 
P0010  Start Quick Commissioning 
0  Ready to Run 
1 Quick Commissioning 
30 Factory Setting 
Note  
P0010 must always be set back to '0' before 
operating the motor. However if P3900 = 1 is set 
after commissioning this is done automatically. 
P0100  Operation for Europe/N. America 
0  Power in kW; f default 50 Hz 
1  Power in hp; f default 60 Hz 
2  Power in kW; f default 60 Hz 
Note 
Settings 0 & 1 can be changed using the 60Hz 
Jum
er to allow 
ermanent settin
. 
P0305 Rated Motor Current
1)
 
0 - 2 x inverter rated current (A) 
Nominal motor current 
A
 from ratin
 
late
P0307 Rated Motor Power
1)
 
0 kW - 2000 kW 
Nominal motor power (kW) from rating plate.  
If P0100 = 1, values will be in hp 
P0310 Rated Motor Frequency
1)
 
12 Hz - 650 Hz 
Nominal motor fre
uenc
 
Hz
 from ratin
 
late
P0311 Rated Motor Speed
1)
 
0  - 40000 1/min 
Nominal motor s
eed 
r
m
 f
om ratin
 
late 
P0700  Selection of Command Source 
2)
 
(on / off / reverse) 
0 Factory Setting 
1  Basic Operator Panel 
2  Terminal / Digital Inputs (Default) 
P1000  Selection of Frequency Setpoint 
2)
 
0  No frequency setpoint 
1.  BOP frequency control ↑↓ 
2. Analogue Setpoint 
27.  Setpoint Addition: Analogue Setpoint & 
Control Potentiometer(Default)  
P1080  Min. Motor Frequency 
Sets minimum motor frequency (0-650Hz) at which 
the motor will run irrespective of the frequency 
setpoint. The value set here is valid for both 
clockwise and anti-clockwise rotation. 
P1082  Max. Motor Frequency 
Sets maximum motor frequency (0-650Hz) at which 
the motor will run at irrespective of the frequency 
setpoint. The value set here is valid for both 
clockwise and anti-clockwise rotation. 
P1120 Ramp-Up Time 
0 s - 650 s 
Time taken for the motor to accelerate from 
standstill up to maximum motor frequency. 
P1121 Ramp-Down Time 
0 s - 650 s 
Time taken for motor to decelerate from maximum 
motor frequency down to standstill. 
P3900  End Quick Commissioning 
0  No Quick Commissioning. 
1  Perform Quick Commissioning with factory reset 
of all other Parameters (Recommended). 
P0304 Rated Motor Voltage
1)
 
10 V - 2000 V 
Nominal motor volta
e 
V
 from ratin
 