EasyManua.ls Logo

Siemens MICROMASTER 411 - Page 77

Siemens MICROMASTER 411
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Issue 03/01 5 System Parameters
MICROMASTER 411 & COMBIMASTER 411 Operating Instructions
6SE6400-5CA00-0BP0
77
Alarms and Warnings (P0004 = 21)
ParNr ParText Default Acc WS QC
P0952 Total number of faults 0 3 CT N
r0947[8] Last fault code - 2 - -
r0949[8] Fault value - 3 - -
r0948[12] Fault time - 3 - -
P2100[3] Alarm number selection 0 3 CT N
P2101[3] Stop reaction value 0 3 CT N
P2111 Total number of warnings 0 3 CT N
r2110[4] Warning number - 2 - -
r2114[2] Run time counter - 3 - -
P2150[1] Hysteresis frequency f_hys 3.00 3 CUT N
P2155[1] Threshold frequency f_1 30.00 3 CUT N
P2156[1] Delay time of threshold freq f_1 10 3 CUT N
P2164[1] Hysteresis frequency deviation 3.00 3 CUT N
P2167[1] Switch-off frequency f_off 1.00 3 CUT N
P2168[1] Delay time T_off 10 3 CUT N
P2170[1] Threshold current I_thresh 100.0 3 CUT N
P2171[1] Delay time current 10 3 CUT N
P2172[1] Threshold DC-link voltage 800 3 CUT N
P2173[1] Delay time DC-link voltage 10 3 CUT N
P2179 Current limit for no load ident. 3.0 3 CUT N
P2180 Delay time for load missing 2000 3 CUT N
r2197 CO/BO: Monitoring word 1 - 2 - -
PI Controller (P0004=22)
ParNr ParText Default Acc WS QC
P2200[1] BI: Enable PID controller 0:0 2 CUT N
P2201[1] Fixed PID setpoint 1 0.00 2 CUT N
P2202[1] Fixed PID setpoint 2 10.00 2 CUT N
P2203[1] Fixed PID setpoint 3 20.00 2 CUT N
P2204[1] Fixed PID setpoint 4 30.00 2 CUT N
P2205[1] Fixed PID setpoint 5 40.00 2 CUT N
P2206[1] Fixed PID setpoint 6 50.00 2 CUT N
P2207[1] Fixed PID setpoint 7 60.00 2 CUT N
P2216 Fixed PID setpoint mode - Bit 0 1 3 CT N
P2217 Fixed PID setpoint mode - Bit 1 1 3 CT N
P2218 Fixed PID setpoint mode - Bit 2 1 3 CT N
r2224 CO: Act. fixed PID setpoint - 2 - -
P2231[1] Setpoint memory of PID-MOP 0 2 CUT N
P2232 Inhibit rev. direct. of PID-MOP 1 2 CT N
P2240[1] Setpoint of PID-MOP 10.00 2 CUT N
r2250 CO: Output setpoint of PID-MOP - 2 - -
P2253[1] CI: PID setpoint 0:0 2 CUT N
P2254[1] CI: PID trim source 0:0 3 CUT N

Table of Contents