5. SYSTEM PARAMETERS International English
MICROMASTER 420 Operating Instructions 85
6SE6400-5AA00-0BP0
Parameter
Number
Parameter Name
Min
Max
[Default]
Units
♦
♦♦
♦P0003 User
Access Level
♦
♦♦
♦P0004 Setting
♦
♦♦
♦Changeable
♦
♦♦
♦Status
Fixed PI setpoint 1
Defines the Fixed PI Setpoint 1
In user access level 2 you will need to set P2200 to enable the setpoint source. In addition
you can set any of the digital input parameters to fixed PI setpoint via the digital inputs
(P0701 – P0703.)
There are three modes of selection for the PI fixed setpoint.
1 Direct selection (P0701 = 15 or P0702 = 15, etc)
In this mode of operation 1 digital input selects 1 fixed PI fixed setpoint.
If several inputs are programmed to PI fixed setpoint and selected together, the selected
setpoints are summed.
To start the motor (enable pulses), an ON command is needed either from the keypad or
from the digital inputs or USS in this mode.
2 Direct selection with ON Command (P0701 = 16 or P0702 = 16, etc)
Description as for 1), except that this type of selection issues an ON command coincident
with any setpoint selection.
Note
You may mix different types of fixed frequencies; remember, however, they will be summed
if selected together.
3 Binary Coded Decimal selection P0701 – P0703 = 17
Using this PI fixed point selection method it is possible to choose up to 7 different PI
setpoints. The setpoints are selected according to the following table:
DIN3 DIN2 DIN1
OFF Inactive Inactive Inactive
P2201 FS. 1 Inactive Inactive Active
P2202 FS. 2 Inactive Active Inactive
P2203 FS. 3 Inactive Active Active
P2204 FS. 4 Active Inactive Inactive
P2205 FS. 5 Active Inactive Active
P2205 FS. 6 Active Active Inactive
P2201
P2207 FS. 7 Active Active Active
-130
130
[0]
%
2
22
‘•’
Fixed PI setpoint 2P2202
Refer to the description in P2201 for Fixed Setpoint 1.
-130
130
[10]
%
2
22
‘•’
Fixed PI setpoint 3P2203
Refer to the description in P2201 for Fixed Setpoint 1.
-130
130
[20]
%
2
22
‘•’
Fixed PI setpoint 4P2204
Refer to the description in P2201 for Fixed Setpoint 1.
-130
130
[30]
%
2
22
‘•’