International English 5. SYSTEM PARAMETERS
86 MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
Parameter
Number
Parameter Name
Min
Max
[Default]
Units
♦
♦♦
♦P0003 User
Access Level
♦
♦♦
♦P0004 Setting
♦
♦♦
♦Changeable
♦
♦♦
♦Status
Fixed PI setpoint 5
P2205
Refer to the description in P2201 for Fixed Setpoint 1.
-130
130
[40]
%
-
2
22
‘•’
Fixed PI setpoint 6P2206
Refer to the description in P2201 for Fixed Setpoint 1.
-130
130
[50]
%
-
2
22
‘•’
Fixed setpoint 7P2207
Refer to the description in P2201 for Fixed Setpoint 1.
-130
130
[60]
%
-
2
22
‘•’
CO: Fixed PI setpointr2224
Displays the total output of the PI fixed setpoint selection.
-130
130
[60]
%
-
2
22
Setpoint Memory of the Motorized Potentiometer (Keypad Setpoint)P2231
0 = setpoint memory disabled.
1 = setpoint memory enabled.
If 0 is selected, the setpoint returns to the value set in P2240 after an OFF command. If 1 is
selected the active setpoint is remembered and P2240 is updated with the current value.
Refer to P2240.
0
1
[0]
-
2
22
‘•’
Inhibit rev. dir. PI-MOP setp.P2232
Inhibits the reverse setpoint selection when keypad (Motorized Potentiometer) is chosen
either as main setpoint or additional setpoint (using P1000)
Possible settings:
0 Reverse direction is allowed – it is possible to change motor direction using the
keypad (Motorized Potentiometer) setpoint (increase / decrease frequency either by
using digital inputs or keypad up / down buttons)
1 Reverse direction inhibited
0
1
[1]
-
2
10
Setpoint PI-MOPP2240
Allows the user to set a digital PI setpoint in %. The setpoint can be changed either by using
the
∆∇ keys on the BOP or by setting P0702 or P0703 to 13 and 14.
-130
130
[10.00]
%
2
22
‘•’
CO: Source of PI setpointr2250
Displays the active digital PI setpoint in %.
-130
130
[10.00]
%
2
22
‘•’
P2253 CI: PI setpoint
0
2248.0
[0]
-
2
22
‘•’